Perancangan Sistem Peringatan Dini Bahaya Kebakaran Berbasis Infrared Fire and Gas Detector dengan Voting Logic 2oo3 dan Verifikasi Safety Integrity Level pada Terminal BBM PT XYZ

Authors

  • Muhammad Fikri Baharuddin Universitas Islam Sultan Agung
  • Eka Nuryanto Budisusila Universitas Islam Sultan Agung Semarang

DOI:

https://doi.org/10.59024/jisi.v4i4.2684

Keywords:

2oo3 Voting, Fire and Gas Detection, Fuel Terminal, LOPA, Safety Integrity Level

Abstract

Fuel terminals store large volumes of volatile hydrocarbons, and a leak can form a flammable vapor cloud that may escalate into a fire or explosion. A root cause analysis at the PT XYZ fuel terminal in Semarang found no fixed vapor cloud detection. This study designs an infrared fire and gas detection-based early warning system that detects leaks, alerts operators, and triggers automatic protection, and verifies its reliability against IEC 61508/61511. Methods include a 5×5 risk matrix, orifice leak rate calculation, Gaussian plume dispersion with 2020–2024 BMKG wind data, 2oo3 voting and electrical design, Layer of Protection Analysis (LOPA), and PFDavg calculation with OREDA data. Leak rates through a 10 mm hole range from 0.32 to 1.45 kg/s, giving conservative 20% LFL hazard radii of 30–66 m. The design uses 22 infrared detectors in five zones with 2oo3 voting on a 1oo2D Safety PLC, lowering the false alarm probability to 0.12% while keeping the sensor PFD at 0.73%. The total PFDavg is 7.53×10−3 (SIL 2) with a risk reduction factor of 133, making it a suitable protection layer for the terminal. The motor operated valve contributes 87.2% of the total PFDavg, making final element redundancy the most effective improvement.

References

American Petroleum Institute. (2018). API RP 505: Recommended practice for classification of locations for electrical installations at petroleum facilities classified as Class I, Zone 0, Zone 1, and Zone 2 (2nd ed.). API.

Arif, M. Z., & Astutik, R. P. (2024). Sistem pendeteksi kebocoran gas pada LPG dan suhu ruangan berbasis protokol MQTT menggunakan metode fuzzy logic. Jurnal Riset Rekayasa Elektro, 6(2), 109. https://doi.org/10.30595/jrre.v6i2.24304

Aulia, I., & Munasir, M. (2022). Rancang bangun alat deteksi kebocoran gas LPG serta penanggulangan kebakaran menggunakan sensor MQ2 dan sensor api berbasis IoT. Jurnal Fisika Unand, 11(3), 306–312. https://doi.org/10.25077/jfu.11.3.306-312.2022

Buncefield Major Incident Investigation Board. (2008). The Buncefield incident 11 December 2005: The final report of the Major Incident Investigation Board (Vol. 1). Health and Safety Executive.

Center for Chemical Process Safety. (2000). Guidelines for chemical process quantitative risk analysis (2nd ed.). American Institute of Chemical Engineers.

Center for Chemical Process Safety. (2001). Layer of protection analysis: Simplified process risk assessment. American Institute of Chemical Engineers.

Crowl, D. A., & Louvar, J. F. (2011). Chemical process safety: Fundamentals with applications (3rd ed.). Prentice Hall.

Fu, L.; You, S.; Li, G.; & Fan, Z. (2023). Enhancing methane sensing with NDIR technology: Current trends and future prospects. Reviews in Analytical Chemistry, 42(1), 20230062. https://doi.org/10.1515/revac-2023-0062

International Electrotechnical Commission. (2010a). IEC 61508: Functional safety of electrical/electronic/programmable electronic safety-related systems (Parts 1–7, 2nd ed.). IEC.

International Electrotechnical Commission. (2010b). IEC 61508-6: Guidelines on the application of IEC 61508-2 and IEC 61508-3 (2nd ed.). IEC.

International Electrotechnical Commission. (2016a). IEC 60079-29-1: Explosive atmospheres - Part 29-1: Gas detectors - Performance requirements of detectors for flammable gases (2nd ed.). IEC.

International Electrotechnical Commission. (2016b). IEC 61511: Functional safety - Safety instrumented systems for the process industry sector (2nd ed.). IEC.

International Electrotechnical Commission. (2023). IEC 60079-11: Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i" (7th ed.). IEC.

International Electrotechnical Commission. (2024). IEC 60079-14: Explosive atmospheres - Part 14: Electrical installations design, selection and installation of equipment, including initial inspection (6th ed.). IEC.

International Society of Automation. (2018). Guidance on the evaluation of fire, combustible gas, and toxic gas system effectiveness (ISA-TR84.00.07-2018). ISA.

Li, D.; Liu, G.; & Mao, Z. (2023). Leak detection and localization in multi-grid space using improved Gaussian plume model. Sensors, 23(13), 6209. https://doi.org/10.3390/s23136209

Liu, R.; Deng, H.-B.; Mou, C.-L.; Wang, L.-Y.; Wang, F.; Xiong, X.-Y.; & Li, Y.-D. (2022). FLACS-based simulation of combustible gases leaked from the pressure device for the optimizing of gas detectors' setup. Safety, 8(3), 53. https://doi.org/10.3390/safety8030053

Mukharror, D. A.; Devianto, H.; & Widyotriatmo, A. (2023). Mining safety integrity level (SIL) determination study results: Evaluating safety integrity level (SIL) targets of 1,109 safety instrumented functions (SIFs) in 12 process facilities in Indonesia. AIP Conference Proceedings, 2879, 020170. https://doi.org/10.1063/5.0126037

Mutiah, T.; Setyawan, A.; Muharam, F.; Rahmi, M.; Fitriyanto; Raharjo, A.; Nurdiansyah, C.; Rafiq, A.; & Hutasoit, K. N. (2023). Respon krisis kebakaran Depo Pertamina Plumpang dalam analisa situational crisis communication theory. NIVEDANA: Jurnal Komunikasi dan Bahasa, 4(1), 37–56. https://doi.org/10.53565/nivedana.v4i1.814

Petrov, A. (2023). Mathematical method of rational placement of gas fire sensors. Sensors, 23(20), 8349. https://doi.org/10.3390/s23208349

Ramezanifar, E.; Gholamizadeh, K.; Mohammadfam, I.; & Mirzaei Aliabadi, M. (2023). Risk assessment of methanol storage tank fire accident using hybrid FTA-SPA. PLoS ONE, 18(3), e0282657. https://doi.org/10.1371/journal.pone.0282657

Republik Indonesia. (2001). Undang-Undang Nomor 22 Tahun 2001 tentang Minyak dan Gas Bumi.

Satria, D. (2023). Sistem peringatan dini kebakaran dan kebocoran gas LPG berbasis notifikasi SMS gateway. Jurnal Informatika, 2(2), 9–13. https://doi.org/10.57094/ji.v2i2.1025

SINTEF & NTNU. (2015). OREDA: Offshore and onshore reliability data handbook (6th ed.). OREDA Participants.

Waworundeng, J. M. S. (2020). Desain sistem deteksi asap dan api berbasis sensor, mikrokontroler dan IoT. CogITo Smart Journal, 6(1), 117–127. https://doi.org/10.31154/cogito.v6i1.239.117-127